Enter and test your program – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 129

Advertising
background image

Publication 1747-UM011G-EN-P - June 2008

Starting Up Your Control System 129

6. Enter and Test Your
Program

After you test all inputs and outputs and they are functioning
properly, follow the steps below to safely and successfully enter and
test your specific application program.

1. Verify the offline program.

After the program has been entered in the offline edit file mode,
program verification may begin.

Remaining in the offline edit file mode, use the cursor keys
and/or search function of your programming device to inspect
every instruction and rung for errors.

2. Check your written program, rung for rung, against the program

entered into the offline memory. The most common errors
found in program entry are:

incorrect addressing of instructions.

omission of an instruction.

more than one output instruction programmed using the
same address.

3. Transfer the program into the processor.

a. Place your programming device online.
b. Place the processor into Program mode.
c. Select the download function when using the Hand-Held

Terminal or the restore function when using your
programming software.

4. Verify the online program transfer.

a. Select monitor file function.
b. Cursor through the program to verify that you selected the

right program.

5. Conduct a single-scan program test.

a. Select the monitor file function and place the cursor on the

first rung.

b. Select the Test mode.
c. Select Single-Scan (SSN) test. In this test mode, the processor

executes a single operating cycle, which includes reading the
inputs, executing the ladder program, and updating all data
without energizing the output circuits. However, the monitor
file function will identify output status as if outputs were
enabled.
Timers are also incremented a minimum of 10 milliseconds
each single scan.

Advertising