Load Initial Configuration Values

Chapter 7

7-30

Comparison of Gain Constants

Compare dependent and independent gains constants as follows:

Dependent Gains Constants:

Independent Gains Constants:

Controller Gain K

c

(dimensionless)

Proportional Gain K

p

(dimensionless)

Reset Term 1/T

i

(minutes per repeat)

Integral Gain K

i

(inverse seconds)

Rate Term T

d

(minutes)

Derivative Term K

d

(seconds)

Other variables used in any algorithm choice include:

Output

= Percentage of full scale

E

= Error (scaled) SP-PV (Setpoint-Process Variable)

PV

= Process Variable (scaled)

Convert from dependent to independent gains constants by substituting
controller gain (K

c

), reset (1/T

i

), and rate (T

d

) values in these formulas:

K

p

= K

c

unitless

K

i

= K

c

60 T

i

inverse seconds

K

d

= K

c

(T

d

)60 seconds

We entered bit B07 = 1 for A-B independent gains on all corresponding
worksheets.

Important: PID gain constants that we entered on worksheets and used in
closed-loop tuning procedures in chapter 10 were independent (A-B) gains.
If, after attempting to tune your pressure loops in chapter 10, you believe
you must use dependent (ISA) gain constants, refer to Section 3 of the
Plastic Molding Module Reference Manual (publication 1771-6.5.88) for
information on this option.