Load Initial Profile Values

Chapter 8

8-4

Clamp Close Profile Block Identifier

(CPC01)
Bits 07-00 of this word identify it as the first word in a series used to
define the clamp close profile. These bits must be set to 00000111.

We entered these bits on Worksheet 8-A.

Velocity Units

(CPC03)
The following bit determines units of measure for velocity values.

- BIT 14 selects units of measure.

0 = Percent velocity
1 = Inches or millimeters per second

We set this bit to 1 for units per second on Worksheet 8-A.

Mold Protection

(CPC03)
The following bit controls the QDC module’s reaction if it moves the
clamp into the mold protection zone while executing 1st or 2nd or 3rd
clamp close.

- BIT 11 determines the QDC modules response to zone overrun.

0 = Start executing low pressure close if zone overrun occurs
1 = Stop and zero outputs if zone overrun occurs

We set this bit to 0 for start executing LPC on Worksheet 8-A.

Logical Bridges

(CPC03)
Logical bridges control the action taken by the QDC module when it
completes a profile.

- BIT 10 controls action at end of third clamp close.

- BIT 09 controls action at end of second clamp close.

- BIT 08 controls action at end of first clamp close.

0 = Start next profile when this profile is complete
1 = Stop and set output when this profile is complete

We set these bits to 0 for start next profile on Worksheet 8-A.

Determine Bit Selections for

Worksheet 8ĆA