Chapter 9

9-35

6.

If the observed pressure HPS16 for pack and HPS33 for hold are still
not within 20% of setpoints HPC16 and HPC33, your pressure valve
is not linear over the desired range. Correct by adjusting the selected
pressure valve, output for minimum PKC43 and HDC43 as follows:

If actuals are at least 20%: And Your Selected

Valve is:

Then change PKC43, HDC43

(N44:159, N44:219) as follows

Less than setpoints

Direct Acting

Increase in 5% steps

Reverse Acting

Decrease in 5% steps

Greater than setpoints

Direct Acting

Decrease in 5% steps

Reverse Acting

Increase in 5% steps

To do this: change PKC43 and HDC43, download PKC, HDC, and
HPC, and repeat steps 3 and 4. Repeat as needed.

Important: If downloading from your programming terminal, download
PKC, HDC, and HPC in that order with bits B21/9, 10, and 11 (chapter 4).

What You Have Accomplished

The open-loop tuning procedure you just completed has defined the:

range of ram (screw) backpressure during plastication

end-of-range maximum and minimum signal levels for linear control of

the plastication pressure valve in open-loop control

For this

range limit

When trying to obtain

the pressure in:

The QDC module drives the selected

pressure valve to % output signal in:

Minimum

PKC41 or HDC41

PKC43 or HDC43

Maximum

PKC42 or HDC42

PKC44 or HDC44

Now for all open-loop pack or hold pressure profiles, the QDC module
assumes a linear relationship between ram pressure and signal outputs.

Set Profile Pressure Alarms

Set profile maximum pressure alarm setpoints PKC57 (N44:173) for pack
and HDC57 (N44:233) for hold to a ram (screw) pressure that should:

not be exceeded during either profile
not be greater than maximum pressure control limits PKC42, HDC42

Entering a value of zero disables these alarms.

Download new values to QDC module by downloading PKC, HDC, HDC.

Important: If downloading from your programming terminal, download
PKC, HDC, and HPC in that order with bits B21/9, 10, and 11 (chapter 4).