Load Initial Configuration Values
Chapter 7
7-40
After you determine your initial values and enter them on configuration
worksheets, you are ready to proceed.
1.
Enter all worksheet values into your PLC-5 data table.
Important: Be sure that you have not altered any setpoints, and that you
have entered each and every setpoint exactly as on the worksheets.
2.
Use the procedure described in chapter 4 to download command
blocks to the QDC module. For your convenience, we repeat the
table of download information (Table 7.B) from chapter 4.
Important: Do not download companion blocks at this time.
Table 7.B
Information Required to Download a Block
Block to
Download:
ProĆSet 600
Block ID.:
ProĆSet 600 Download
Command Bit in B21:
FCC
03
2
SCC
04
3
TCC
05
4
LPC
06
5
INC
08
7
PKC
10
9
HDC
11
10
PLC
14
13
FOC
17
16
SOC
18
17
TOC
19
18
OSC
20
19
Enter and Download your
Worksheet Values