Load Initial Profile Values

Chapter 8

8-22

Cure Timer Preset

(HPC61)
Use this word to set the length of cure time that starts at completion of the
hold profile. You enter this preset in seconds (000.0 to 999.9). After the
QDC module starts the internal cure timer, it:

reports the accumulated value of the timer in SYS58
sets bit SYS03-B03 when the timer is timing
sets the done bit SYS03-B05 when SYS58 equals or exceeds HPC61
stops this timer when:

SYS58 = 999.9 seconds, or when
it sees a false-to-true transition of DYC03-B01

resets SYS58 to zero on a false-to-true transition of DYC03-B01

We entered zero for this preset on Worksheet 8-C.

The valve spanning procedures in chapter 9 require these initial values.
We help you select correct final values for your application in chapter 10.
For additional information, refer to the Plastic Molding Module Reference
Manual (publication 1771-6.5.88).

After you determine initial values and enter them on Worksheet 8-C, you
are ready to proceed.

1.

Enter all worksheet values into your PLC-5 data table.

Important: Be sure that you have not altered any setpoints, and that you
have entered each and every setpoint exactly as on the worksheet.

2.

Use the procedure described in chapter 4 to download command
blocks to the QDC module. We repeat the HPC block download data:

Block

Block ID

Command Bit

Companion

HPC

12

B21/11

none

3.

Check SYS61 and SYS62 for programming errors. Correct as needed.

Enter and Download your

Worksheet Values