Chapter 2

2-9

Analog inputs and outputs are sensitive to electrical noise interference.
Take care to shield them properly.

Guidelines:

Use 22-gage (or larger) twisted-pair cable, 100% shielded with drain

wire, such as Belden 8761. For cable distances over 50 ft, use 18-gage
cable such as Belden 8760.

Ground the cable shield at one end only; generally at the sensor or

amplifier end of the cable, not at the I/O chassis (see Figure 2.4 and
Figure 2.5)

Figure 2.4

Shielding Differential Inputs

Connect the cable shield

and case ground to earth

ground at the Input Sensor

Input Sensor

18

17

14

QDC Module Input

Input Module Common

should float

+

10910Ć2

+15V

-15V

No User Connectiions.

For Test Purposes, only.

Ground and Shield

Your I/O Devices