Rockwell Automation 1771-QDC, D17716.5.86(Passport) PLASTIC MOLDING MODULE User Manual

Page 196

Advertising
background image

Span Your Valves

Chapter 9

9-39

9.

Observe and record actual backpressures reported by the QDC
module for all profile segments in PPS10, 14, 18, 22, 26, 30, 34 etc.
(N44:714, 718, 722, 726, 730, 734, 738, 742, 746, 750, 754).

10.

Compare actual backpressures with your setpoints in
PPC10, 14, 18, 22, 26, 30, 34, 38, 42, 46, 50 as follows:

If

Then

Actuals are greater than

setpoints by 20% or more

1. Decrease PLC44 by 10%.

2. Enter this new value into PLC data table.

3. Repeat the profile with steps 7Ć9.

4. Repeat these adjustments until actuals

just drop below setpoints.

Actuals are less than

setpoints by 20% or more

1. Increase PLC44 by 10%.

2. Enter this new value into PLC data table.

3. Repeat the profile with steps 7Ć9.

4. Repeat these adjustments until actuals

are equal to or greater than setpoints.

Actuals are less than

setpoints by 20% and PLC44 = 100%

1. Decrease PLC42 by 10%.

2. Enter this new value into PLC data table.

3. Repeat the profile with steps 7Ć9.

4. Repeat these adjustments until actuals

are equal to or greater than setpoints.

Test Valve Linearity with a Plastication Backpressure Profile

1.

Change backpressure setpoints to 1/2 PLC44 (1/2 Max Control Limit)
in PPC10, 14, 18, 22, 26, 30, 34, 38, 42, 46, and 50
(in N44:426, 430, 434, 438, 442, 446, 450, 454, 458, 462, 466).

2.

Download the PLC and PPC blocks to the QDC module.

Important: If downloading from your programming terminal, download
PLC followed by PPC with download bits B21/13 and 14 (chapter 4).

3.

Run an open-loop backpressure vs. position profile. Do this by
toggling DYC02-B08 (B34/408) from 0 to 1 to 0.

4.

Compare backpressures reported in middle segments 5, 6, and 7 in
PPS26, 30, 34 (N44:730, 734, 738) with setpoints PLC26, 30, and 34.
Adjust PLC41 or PLC43 as follows:

If actual backpressures are:

And Your Selected

Valve is:

Then change PLC41 or 43

(N44:397 or 399) as follows:

Greater than or equal to setpoints Either one

Increase PLC41 in 5% steps

Less than setpoints

Direct Acting

Increase PLC43 n 5% steps

Reverse Acting

Decrease PLC43 in 5% steps

Advertising