Chapter 9

9-50

Test Valve Linearity with a Velocity vs. Position Profile

1.

Select velocity vs. position control for the entire clamp open
operation by resetting the following bits to zero:

OPC03-B00 (B37/608)
OPC03-B02 (B37/610)
OPC03-B04 (B37/612)
OPC03-B06 (B37/614)

2.

Download this change to the QDC module.

Important: If downloading from your programming terminal, download
OPC by setting download bit B21/20 (chapter 4).

3.

Jog your clamp to the full close position (mold halves mated).

4.

Enable first clamp open by setting DYC02-B10 (B34/410) to 1. The
clamp should move from its start position through the first clamp
open profile, and then execute open slow. If no motion is observed,
verify that:

- no overtravel alarms are set. The QDC module inhibits clamp

open if SYS07-B00 through -B05 are set

- no programming error codes exist in SYS61 and SYS62

5.

Upon completion of clamp open, observe the velocity reported for 1st
clamp open segment 2 in OPS12 (N43:720). This velocity should be
relatively close to the setpoint you entered in OPC12 (N43:548). If
the observed velocity is not within 25% of the setpoint, verify that:

- you choose the correct values from your flow rate curves

- your calculations are correct

If the observed velocity OPS12 is still not within 20% of OPC12, your
pressure valve is not linear over the desired range. Correct as follows:

If:

And Your

Selected Valve is:

Then change FOC48

(N43:344) as follows:

OPS12 was less than OPC12

Direct Acting

Increase by 5%

Reverse Acting

Decrease by 5%

OPS12 was more than

OPC12

Direct Acting

Decrease by 5%

Reverse Acting

Increase by 5%

To do this: change FOC48, download the FOC and OPC blocks, and repeat
steps 3-5. Repeat as necessary.

Important: If downloading from your programming terminal, download
FOC followed by OPC with download bits B21/16 and 20 (chapter 4).