Enter Your PressureĆalarm and TimeĆdelay Values Here

Configure the QDC Module's I/O

Chapter 3

3-16

Set Up Maximum Pressure Alarms and Time Delays

The QDC module continuously monitors ram (screw) and clamp pressure
inputs. When it detects that the process input equals or exceeds a preset
alarm setpoint, the QDC module sets an alarm bit. A setpoint of zero
disables the associated alarm.

To guard against nuisance alarms caused by noise spikes or pressure
transients, you can set a time delay so the QDC module must monitor
continuous excessive pressure for an amount of time before setting the
high pressure alarm. A setpoint of zero disables this delay.

Configure the QDC module for pressure alarms as follows:

1.

Determine these values for ram (screw) and/or clamp pressure
alarms:

pressure-alarm setpoint
time-delay setpoint

2.

Record non-zero setpoints on Worksheet 3-G for the pressure alarms
and time delays you want to use.

3.

Download them to the QDC module using the procedures presented
earlier in this chapter.

Worksheet 3ĆG

PressureĆalarm and TimeĆdelay Setpoints

Control Word

ProĆSet 600 Addr. Value

Description

Units

MCC21

N40:17

Screw PressureĆalarm Setpoint

Ram (screw) Pressure

2

MCC22

N40:18

ScrewĆpressure TimeĆdelay Setpoint

Time Measured in Seconds

1

MCC35

N40:31

Clamp PressureĆalarm Setpoint

Clamp Pressure

2

MCC36

N40:32

ClampĆpressure TimeĆdelay Setpoint

Time Measured in Seconds

1

1

Time Measured in Seconds

2

Pressure

00.00 to 00.99

0000 to 9999 PSI

000.0 to 999.9 Bar