Install the QDC Module
Chapter 2
2-4
Table 2.A
Jumper Settings
Jumper:
Function:
Setting:
E1
Run/Calibrate
Calibrate = right
Run = left
1
E5
I/O Density
Standard = top
1
Do not use bottom position
E6
E7
E8
E9
Input 1 (Screw position)
Input 2 (Screw pressure)
Input 3 (Clamp position)
Input 4 (Clamp pressure)
Voltage = right
1
Current = left
E10
E14
E13
E17
Output 1 (Valve 1)
Output 2 (Valve 2)
Output 3 (Valve 3)
Output 4 (Valve 4)
Current = top
Voltage = bottom
1
E11
E12
E15
E16
Output 1 (Valve 1)
Output 2 (Valve 2)
Output 3 (Valve 3)
Output 4 (Valve 4)
-10 to +10 Vdc = top
0 to +10 Vdc or
4 to 20mA = bottom
1
1
Factory Defaults
Important: If you select current output with jumper plugs E10, E14, E13,
and/or E17, then you must select the 4 to 20mA jumper position with E11,
E12, E15, and/or E16.
ATTENTION: If an output is unconnected, set the jumper
(E11, E12, E15, and/or E16) that corresponds to that output to
0 - 10 Vdc (bottom position). Setting the jumpers for –10 to
+10 Vdc and later configuring the output as “unconnected”
causes the QDC module to output –10 Vdc on that channel
when a system reset occurs and all outputs are forced to 0%
(i.e. 0% output equals –10 Vdc).