Publication 1760-UM003A-EN-P - September 2005

1-2 Pico DeviceNet Interface

Structure of the Unit

Figure 1.2

Communication Profile

• Predefined master/slave communication settings

The I/O polling connection is used for the transfer of 3 bytes

of input data (R1 to R16) and 3 bytes of output data (S1 to S8)
between the base unit with gateway interconnection and the
DeviceNet programmable controller.

The I/O Change of State/Cyclic connection (acknowledged,

unacknowledged) is used to transfer 2 bytes of diagnostic
data from the control relay to the DeviceNet programmable
controller.

The explicit connection set-up is used for read/write access

to function relay parameters in the control relay. This type of
connection set-up also supports the configuration, diagnostics
and management services of the control relay.

• DeviceNet Communication adapter profile (device type 12),

which has been expanded by requests

• Group 2 server
• UCMM-capable device
• Dynamic set-up of explicit and I/O connections are possible
• Device Heartbeat Message
• Device Shutdown Message
• Offline communication settings

Hardware and Operating
System Requirements

The 1760-DNET expansion unit operates together with Pico Series B
and Pico GFX-70 controllers.

MS

NS

a

b

d

e

f

c

1

Pico-Link Socket

2

5-pin DeviceNet Connector

3

24V dc Power Supply

4

Equipment Rating Plate

5

Network Status LED

6

Module Status LED