Read/write date and time, Read/write date and time -2 – Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual

Page 46

Advertising
background image

Publication 1760-UM003A-EN-P - September 2005

6-2 Application Examples for Pico

The master transmits a control command to initiate data exchange
between the communication partners. The slave always returns an
answer to this request, which indicates whether data has been
exchanged or not. An error code will be returned if data exchange has
failed. This code is defined in the ODVA specifications. (see Related
Documentation
on page P-2)

Read/Write Date and Time

IMPORTANT

The operating mode of the basic unit must
correspond with the status indicated at the LEDs
when the various parameters are being set.

Table 6.1 Telegram Structure

Byte

Description

Value (Hex), Sent by

Master

Slave

Master Slave

Attribute ID
Read

93

-

Attribute ID
Write

B3

-

0

Read
Successful

-

C2

Write
Successful

-

C1

Command
Rejected

-

C0

0

1

Len

05

05

1

2

Index

0 to 2

(1)

(1) 0 = Time/date , 1 = Summer time, 2 = Winter time

0 to 2

(1)

2 to 6

3 to 7

Data 1 t o5

Depending on
index

Depending on
index

Table 6.2 Index 0 - Date and Time of Real-Time Clock

Byte

Content

Operand

Value (Hex)

Master

Slave

2

3

Data 1

Hour

0 to 23

0x00 to 0x17h

3

4

Data 2

Minute

0 to 59

0x00 to 0x3Bh

Advertising