Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual
Page 70
![background image](/manuals/579693/70/background.png)
Publication 1760-UM003A-EN-P - September 2005
6-26 Application Examples for Pico
Example:
Data 1 (Byte 4) = 0x01
Meaning:
The values appear in the Parameter menu.
1
2
Instance
(1)
00 – 03
00 – 03
2
3
Index
Table 6.49
Table 6.49
3 – 6
4 – 7
Data 1 – 4
depending on
index,Table 6.50
depending on
index,Table 6.50
(1) Pico provides 4 operating hours counters O1 to O4. These can be addressed using the instance (0 – 3).
(2) Possible causes page 6-34
Table 6.49 Operand overview
Index
(hex)
Operand
Read
Write
00
Parameters Table 6.50
x
01
Control byte Table 6.51
x
02
Process variable
S1
(1)
(1) A 32-bit value is transferred in data bytes Data 1 – Data 4. It should be remembered that the Data
1 is the low byte and Data 4 the high byte.
x
c
(2)
(2) The value can only be written if it is assigned to a constant in the program.
03
Counter setpoint 2
S2
2
x
c1
Table 6.50 Index 00 – Parameters
Meaning
Bit 7
6
5
4
3
2
1
0
Appears in the parameter menu
Yes/no
0/1
Use in the program
Setpoint S1
0/1
Unused bits
–
–
–
–
–
–
Table 6.48 Telegram Structure
Byte
Meaning
Value (hex), sent by
Master Slave
Master
Slave