Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual

Page 70

Advertising
background image

Publication 1760-UM003A-EN-P - September 2005

6-26 Application Examples for Pico

Example:

Data 1 (Byte 4) = 0x01

Meaning:

The values appear in the Parameter menu.

1

2

Instance

(1)

00 – 03

00 – 03

2

3

Index

Table 6.49

Table 6.49

3 – 6

4 – 7

Data 1 – 4

depending on
index,Table 6.50

depending on
index,Table 6.50

(1) Pico provides 4 operating hours counters O1 to O4. These can be addressed using the instance (0 – 3).

(2) Possible causes page 6-34

Table 6.49 Operand overview

Index
(hex)

Operand

Read

Write

00

Parameters Table 6.50

x

01

Control byte Table 6.51

x

02

Process variable

S1

(1)

(1) A 32-bit value is transferred in data bytes Data 1 – Data 4. It should be remembered that the Data

1 is the low byte and Data 4 the high byte.

x

c

(2)

(2) The value can only be written if it is assigned to a constant in the program.

03

Counter setpoint 2

S2

2

x

c1

Table 6.50 Index 00 – Parameters

Meaning

Bit 7

6

5

4

3

2

1

0

Appears in the parameter menu

Yes/no

0/1

Use in the program

Setpoint S1

0/1

Unused bits

Table 6.48 Telegram Structure

Byte

Meaning

Value (hex), sent by

Master Slave

Master

Slave

Advertising