Publication 1760-UM003A-EN-P - September 2005

Pico GFX Control Commands 7-47

The data in the following table is shown in the Motorola format
although it is actually transferred in Intel format.

Example

The channel A parameters of 7-day time switch HW19 are to be read.

Table 6.152 Operand overview

Index
(hex)

Operand

read

write

00

Bit IO

Table 6.153

x

01

Mode/Parameter

02

Parameters Table 6.154

x

Channel A

03

Channel B

04

Channel C

05

Channel D

Table 6.153 Index 0 – Bit IO

FB output Data 3

Bit

7

6

5

4

3

2

1

0

Q

(1)

(1) Status 1 if the switch-on condition is fulfilled.

Table 6.154 Index 2 – 5, Parameter channels A – D

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Date 2

Date 1

ON

d4

(1)

(1) d5 to d0: Weekday (0 = Sunday to 6 = Saturday)

d3 d2 d1 d0 h4

(2)

(2) h4 to h0: Hour (0 to 23)

h3 h2 h1 h0 m5

(3)

(3) m5 to m0: Minute (0 to 59)

m4 m3 m2 m1 m0

Weekday

Hour

Minute

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Date 4

Date 3

OFF d4

d3 d2 d1 d0 h4

h3 h2 h1 h0 m5

m4 m3 m2 m1 m0

Weekday

Hour

Minute