Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual
Page 127

Publication 1760-UM003A-EN-P - September 2005
Pico GFX Control Commands 7-47
The data in the following table is shown in the Motorola format
although it is actually transferred in Intel format.
Example
The channel A parameters of 7-day time switch HW19 are to be read.
Table 6.152 Operand overview
Index
(hex)
Operand
read
write
00
Bit IO
Table 6.153
x
01
Mode/Parameter
–
–
02
Parameters Table 6.154
x
Channel A
03
Channel B
04
Channel C
05
Channel D
Table 6.153 Index 0 – Bit IO
FB output Data 3
Bit
7
6
5
4
3
2
1
0
–
–
–
–
–
–
–
Q
(1)
(1) Status 1 if the switch-on condition is fulfilled.
Table 6.154 Index 2 – 5, Parameter channels A – D
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 2
Date 1
ON
d4
(1)
(1) d5 to d0: Weekday (0 = Sunday to 6 = Saturday)
d3 d2 d1 d0 h4
(2)
(2) h4 to h0: Hour (0 to 23)
h3 h2 h1 h0 m5
(3)
(3) m5 to m0: Minute (0 to 59)
m4 m3 m2 m1 m0
Weekday
Hour
Minute
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 4
Date 3
OFF d4
d3 d2 d1 d0 h4
h3 h2 h1 h0 m5
m4 m3 m2 m1 m0
Weekday
Hour
Minute