Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual

Page 68

Advertising
background image

Publication 1760-UM003A-EN-P - September 2005

6-24 Application Examples for Pico

Example:

Data 1 (Byte 4) = 0x07

Meaning:

The values appear in the Parameter menu. The counter is used in the
mode of the frequency meter. The counter setpoint 1 is not assigned
to a constant and cannot therefore be written to.

Table 6.44 Operand overview

Index
(hex)

Operand

Read

Write

00

Parameters Table 6.45

x

01

Control byte Table 6.46

x

02

Process variable

S1

(1)

(1) A 16-bit value is transferred in data bytes Data 1 – Data 2. It should be remembered that

Data 1 is the low byte and Data 2 the high byte.

x

c

(2)

(2) The value can only be written if it is assigned to a constant in the program.

03

Counter setpoint 2

S2

(1)

x

c

(2)

Table 6.45 Index 00 – Parameters

Meaning

Bit 7

6

5

4

3

2

1

0

Appears in the parameter menu

Yes/no

0/1

Counter mode

FB not used

0

0

Up/down counter (N)

0

1

High-speed up/down counter (H)

1

0

Frequency counter (F)

1

1

Use as constant and therefore can be written to

Counter setpoint S1

0/1

Unused bits

Table 6.46 Index 01 – Control byte

Data 1

Bit

7

6

5

4

3

2

1

0

FB output

C

(1)

(1) Count coil, counts on every rising edge

RE

(2)

(2) Reset, the timing relay is reset (reset coil)

D

(3)

(3) Count direction: 0 = up counting, 1 = down counting

Q1

(4)

(4) Switch contact

Advertising