4-6 DeviceNet Functions

DeviceNet Object

The DeviceNet object instance is used to configure the
communication module and to define the physical environment. The
Service Codes used for the Identity Object also apply in this case.

Pico Object

The Pico object can be used to access Pico/GFX functions via the
DeviceNet communication bus . The table below shows the attributes

Object Address

Function

Access

Class ID

Instance ID

Attribute ID

Service Code

03

hex

01

hex

Table 4.6

Table 4.5

Table 4.6 DeviceNet Object Instance Attribute IDs

Attribute
ID

Access Name

Description

Size
(byte)

1

Read/
Write

MAC ID

The MAC ID represents the network
address of a network node. It can be read
and set for the module via the DeviceNet
fieldbus by means of this attribute. Range
of values: 0 to 63

dec

. (see DeviceNet

Setting the Slave Address on page 3-1)

1

2

Read/
Write

Baud rate

This attribute can be used to read/set the
data transfer rate for communication
functions. Range of values: 0 to 2, 125 to
500 kbps (see Data Transfer Rates –
Automatic Baud Rate Recognition on page
2-4)
.

1

3

Read/
Write

BOI (Bus-Off
interrupt)

This attribute can be used to define the
reaction to a Bus-Off event (CAN-specific).

1

4

Read/
Write

Bus-Off
counter

This values shows how often a Bus-Off
event has occurred. Range of values: 0 to
255.

1

Object Address

Function

Access

Class ID

Instance ID

Attribute ID

Service Code

64

hex

01

hex

Table 4.7

Table 4.8

Advertising