Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual
Page 97

Publication 1760-UM003A-EN-P - September 2005
Pico GFX Control Commands 7-17
Local outputs: QW0/
outputs of the network station: QW1 – QW8
The local outputs can be read directly via DeviceNet, and from Pico
GFX version 04 they can also be written. However, the outputs are
only switched externally if the device is in Run mode and the
addressed output is not being used in the circuit diagram. Refer
to Read/write image data on page 7-7.
Table 6.92 Telegram Structure
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave
Attribute ID
Read
91
–
Write
(1)
(1) Writing is only possible from Pico GFX, device version 04 see Read/write date and time on page 7-2..
B1
–
0
Answer
Read successful
–
C2
Write successful
–
C1
Command rejected
–
C0
0
1
Len
02
02
1
2
Type
04
04
2
3
Index
(2)
(2)
00 = Local output 01 – 08 = Outputs of network stations 1 – 8
00/01 – 08
00/01 – 08
3
4
Data 1
Read operation
00
Table 6.81
Write operation
00
4 – 6
5 – 7
00
00
Table 6.93 Byte 4: Data
Data 1
Bit
7
6
5
4
3
2
1
0
Q1
0/1
Q2
0/1
Q3
0/1
Q4
0/1
Q5
0