Publication 1760-UM003A-EN-P - September 2005

6-28 Application Examples for Pico

Example:

Data 1 (Byte 4) = 0xAC

Table 6.53 Operand overview

Index
(hex)

Operand

Read

Write

00

Parameters Table 6.54

x

01

Control byte Table 6.55

x

02

Actual value 1

T

x

c

(2)

(2) The value can only be written if it is assigned to a constant in the program.

03

Time setpoint 1

S1

(1)

(1) A 16-bit value is transferred in data bytes Data 1 – Data 2. It should be remembered that Data 1 is the low byte

and Data 2 the high byte.

x

c

(2)

04

Time setpoint 2

S2

(1)

x

c

(2)

Table 6.54 Index 00 – Parameters

Meaning

Bit 7

6

5

4

3

2

1

0

Appears in the parameter menu

Yes/no

0/1

Timer mode

On-delayed,

0

0

0

off-delayed.

0

0

1

On-delayed with random setpoint

0

1

0

Off-delayed with random setpoint

0

1

1

On and off delayed

(two time setpoints)

1

0

0

On and off delayed each with random
setpoint (two time setpoints)

1

0

1

Impulse transmitter

1

1

0

Flashing relay (two time setpoints)

1

1

1

Timebase

FB not used

0

0

Millisecond: S

0

1

Second: M:S

1

0

Minute: H:M

1

1

Use as constant and therefore can be written to

Time setpoint S1

0/1

Time setpoint S2

0/1