Read/write image data, Read/write image data -7, Overview local analog inputs: ia1 – ia4 – Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual

Page 87

Advertising
background image

Publication 1760-UM003A-EN-P - September 2005

Pico GFX Control Commands 7-7

Read/write image data

Overview

Local analog inputs: IA1 – IA4

The analog inputs on the Pico GFX and GFX basic units can be read
directly via DeviceNet. The 16-bit value is transferred in Intel format
(Low Byte first).

Table 6.75

Operands

Meaning

Read/Write Command

(hex)

Page

IA1 – IA4

“Local analog inputs: IA1 – IA4“

read

02

7

ID1 – ID16

“Local diagnostics: ID1 – ID16“

read

03

9

IW0

“Read local inputs: IW0“

read

01

10

IW1 – IW8

“Inputs of the network station: IW1 –
IW8“

read

01

11

M...

“Marker: M..“

read/write

0B – 0E

12

P1 – P4

“Local P buttons: P1 – P4“

read

06

15

QA1

“Local analog output: QA1“

read/write

05

16

QW0,
QW1 –
QW8

“Local outputs: QW0/ outputs of the
network station: QW1 – QW8“

read/write

04

17

R1 – R16

S1 – S8

“Inputs/outputs of PicoLink: RW/SW“

read

07/09

18

RN1 –
RN32

SN1 –
SN32

“Receive data network: RN1 – RN32/
Send data network: SN1 – SN32“

read

08/0A

19

Table 6.76 Telegram Structure

Byte

Meaning

Value (hex), sent by

Master

Slave

Master

Slave

Attribute ID: Read

91

0

Response:

Read successful

C2

Command rejected

C0