Publication 1760-UM003A-EN-P - September 2005

7-14 Pico GFX Control Commands

Example 1: Set/reset market bit

Marker bit 62 should be set or reset. Write a “1” to set or a “0” to reset
the marker bit in the least significant bit of data byte “Data 1”.

Example 2: Write marker word

The value 823 should be written into the marker word MW32: 823

dec

= 337

hex

r Data 1 = 37

hex

, Data 2 = 03

hex

Table 6.87

Byte

Meaning

Value (hex), sent
by

Master

Slave

Master

Slave

Attribute ID: Write

B1

0

Response: Write successful

C1

0

1

Len

01

01

1

2

Type

0B

0B

2

3

Index

3E

3E

3 4

Data

1

010

(1)

(1) 01 = set, 00 = reset

00

4 – 6

5 – 7

Data 2 – 4

00

00

Table 6.88

Byte

Meaning

Value (hex), sent by

Master

Slave

Master

Slave

Attribute ID: Write

B1

0

Response: Write successful

C1

0

1

Len

01

01

1

2

Type

0D

0D

2

3

Index

20

20

3

4

Data 1

37

00

4 5

Data

2

03

00

5

6

Data 3

00

00

6

7

Data 4

00

00