6-16 Application Examples for Pico

Example:

Data 1 = 52

hex

l Q2, Q5 and Q7 are active.

Inputs/outputs of PicoLink: R1 – R16/S1 – S8

This service allows you to read the local R and S data and the data of
the NET stations (1 – 8) transferred via PicoLink, again from the
relevant Pico image.

Q2

0/1

..

..

Q8

0/1

Table 6.28 Telegram Structure

Byte

Meaning

Value (hex), sent by

Master

Slave

Master

Slave

Attribute ID: Read

88

0

Response:

Read successful

C2

Command
rejected

C0

(1)

(1) Possible causes page 6-34

0

1

Len

01

01

1

2

Type

for R data

88

88

for S data

89

89

2

3

Index

00

00

3

4

Data 1 (Low Byte)

00

Table 6.29

4

5

Data 2 (Low Byte)

00

Table 6.29

5 – 6

6 – 7

Data 3 – 4

00

00

Table 6.29 Byte 3 to 4 (master) or Byte 4 to 5 (slave): Data 1 to 2

Data 1

Bit

7

6

5

4

3

2

1

0

RW

SW

R1

S1

0/1

R2

S2

0/1

...

...

...

Table 6.27 Byte 4: Data 1