A-2 Specifications

Shocks (IEC 60068-2-27) semi-sinusoidal 15
g/11 ms

18 Shocks

Drop (IEC 60068-2-31) height

50 mm

Free fall, when packed (IEC 60068-2-32)

1 m

Table A.4 Electromagnetic Compatibility (EMC)

Description

Specification

Electrostatic discharge (ESD), (IEC/EN
61000-4-2, severity level 3)
Air discharge

8 kV

Electrostatic discharge (ESD), (IEC/EN
61000-4-2, severity level 3)
Contact discharge

6 kV

Electromagnetic fields RFI),
(IEC/EN 61000-3

10 V/m

Radio interference suppression (EN 55011,
EN 55022), class

B

Burst (IEC/EN 61000-4-4, severity level 3)
Power cables

2 kV

Burst (IEC/EN 61000-4-4, severity level 3)
Signal cables

2 kV

High energy pulses (Surge) (IEC/EN
61000-4-5), power cable symmetrical

1 kV

High-energy pulses (surge) of DC current
(IEC/EN 61 000-4-5, severity level 2), power
cable symmetrical

0.5 kV

Line-conducted interference (IEC/EN
61000-4-6)

10 V

Table A.5 Dielectric Strength

Description

Specification

Measurement of the clearance and
creepage distance

EN 50178, UL508, CSA C22.2 No. 142

Dielectric strength

EN 50 178