Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual
Page 65

Publication 1760-UM003A-EN-P - September 2005
Application Examples for Pico 6-21
• The maximum data length is 4 bytes. All values must be
transferred in hexadecimal format.
Overview
Analog value comparator/threshold comparator: A1 – A16
Table 6.38 Overview
Operands
Meaning
Read/Write
Type
(hex)
Page
A1 – A16
„Analog value comparator/threshold
comparator: A1 – A16“
Read/Write
8D
21
C1 – C16
„Counter relays: C1 – C16“
Read/Write
8F
23
O1 – O4
„Operating hours counters: O1 – O4“ Read/Write
92
25
T1 – T16
„Timing relays: T1 – T16“
Read/Write
8E
27
Y1 – Y8
„Year time switch: Y1 – Y8“
Read/Write
A2
30
Ц
1 –
Ц
8
7-day time switch:
Ц
1 –
Ц
8
Read/Write
A1
32
Table 6.39 Telegram Structure
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave
Attribute ID
Read
89
–
Write
8D
–
0
Response:
Read successful
–
C2
Write successful
–
C1
Command rejected
–
C0
(2)
(2) Possible causes page 6-34
0
1
Type
8D
8D
1
2
Instance
(1)
(1) Pico provides 16 analog comparators A1 to A16 for use as required. These can be addressed using the instance
(0 – F).
00 – 0F
00 – 0F
2
3
Index
Table 6.40
Table 6.40
3 – 6
4 – 7
Data 1 – 4
depending on
index,Table 6.41
depending on
index,Table 6.41