7-28 Pico GFX Control Commands
Boolean operation: BV01 – BV32
Table 6.113 Index 0 – Bit IO
Bit
7
6
5
4
3
2
1
0
FB input Data 1
–
–
–
–
–
–
–
T
(3)
(3) Transfer of the source address specified at I1 to the target address specified at I2 on rising edge.
FB output Data 3
–
–
–
–
–
E3
(1)
(1) Status 1 if the number of elements exceeds the source or target range.
E2
(2)
(2) Status 1 if the source and target range overlap.
E1
(4)
(4) Status 1 if the source or target range are outside of the available marker range (offset error)
Table 6.114 Index 1 - Mode
Data 1
(hex)
Mode
00
INI: Initialises the target range with a byte value stored at the source
address.
01
CPY: Copies a data block from a source to a target range. Data block size
is specified at NO.
Table 6.115 Telegram Structure
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave
Attribute ID
Read
92
–
Write
B2
–
0
Response:
Read successful
–
C2
Write successful
–
C1
Command rejected –
C0
0
1
Type
13
13
1
2
Instance
01 – 20
01 – 20
2
3
Index
Table 6.116
Table 6.116