7-42 Pico GFX Control Commands

Write successful

C1

Command
rejected

C0

0

1

Type

27

27

1

2

Instance

01 – 20

01 – 20

2

3

Index

Table 6.141

Table 6.141

3 – 6

4 – 7

Data 1 – 4

Read operation

00

depending on index,
Table 6.142, 6.143

Write operation

depending on index,
Table 6.142, 6.143

Table 6.141 Operand overview

Index
(hex)

Operand

read write

00

Bit IO, Table 6.142

x

01

Mode, 6.143

x

02

Setpoint: –32768 to +32767

I1

x

c

(1)

(1) The value can only be written if it is assigned to a constant in the program.

03

Actual value: –32768 to +32767

I2

x

c

(1)

04

Proportional gain

[%], Value range: 0 to 65535

KP

x

c

(1)

05

Reset time [0.1 s], Value range: 0 to 65535

TN

x

c

(1)

06

Rate time [0.1 s], Value range: 0 to 65535

TV

x

c

(1)

07

Scan time = Time between function block calls.

Value range: 0.1s to 6553.5s.
If 0 is entered as the value, the scan time will be
determined by the program cycle time.

TC

x

c

(1)

08

Manual manipulated variable, value range: –4096 to
+4095

M
V

x

c

(1)

09

Manipulated variable

QV

x

• Mode: UNI, value range: 0 to +4095 (12 bit)
• Mode: BIP, value range: –4096 to +4095 (13 bit)

Table 6.140 Telegram Structure

Byte

Meaning

Value (hex), sent by

Master

Slave

Master

Slave