7-42 Pico GFX Control Commands
Write successful
–
C1
Command
rejected
–
C0
0
1
Type
27
27
1
2
Instance
01 – 20
01 – 20
2
3
Index
Table 6.141
Table 6.141
3 – 6
4 – 7
Data 1 – 4
Read operation
00
depending on index,
Table 6.142, 6.143
Write operation
depending on index,
Table 6.142, 6.143
Table 6.141 Operand overview
Index
(hex)
Operand
read write
00
Bit IO, Table 6.142
x
01
Mode, 6.143
x
02
Setpoint: –32768 to +32767
I1
x
c
(1)
(1) The value can only be written if it is assigned to a constant in the program.
03
Actual value: –32768 to +32767
I2
x
c
04
Proportional gain
[%], Value range: 0 to 65535
KP
x
c
05
Reset time [0.1 s], Value range: 0 to 65535
TN
x
c
06
Rate time [0.1 s], Value range: 0 to 65535
TV
x
c
07
Scan time = Time between function block calls.
Value range: 0.1s to 6553.5s.
If 0 is entered as the value, the scan time will be
determined by the program cycle time.
TC
x
c
08
Manual manipulated variable, value range: –4096 to
+4095
M
V
x
c
09
Manipulated variable
QV
x
• Mode: UNI, value range: 0 to +4095 (12 bit)
• Mode: BIP, value range: –4096 to +4095 (13 bit)
Table 6.140 Telegram Structure
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave