Table 8.199
Module Status LED MS
Possible Cause
Correction
OFF
No power at module.
Switch on the power supply.
Green
module is in standby mode.
None
Green flashing
module not configured.
Verify the correct setting of
the MAC ID.
Red flashing
Invalid configuration
Check configuration data.
RED
Module error which can not
be resolved.
Replace the module.
Table 8.200
Network Status LED NS
Possible Cause
Correction
OFF
module without power or
communication is blocked at
this channel because
of bus-off state or
power loss or
the channel was
blocked explicitly.
Switch on the module,
supply the mains voltage to
the channel and
ensure that the channel is
active.
Green
Although the channel is
enabled, communication is
not possible.
Check the communication
function at the master
programmable controller.
Green flashing
Normal mode
None
Red flashing
Communication error or the
module may be defective.
Reset the module. If further
errors occur, replace the
module.
RED
Communication error.
Check the master
programmable controller.