8 - troubleshoot your controller, Chapter 8, Troubleshoot your controller – Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual

Page 147: Chapter

Advertising
background image

1

Publication 1760-UM003A-EN-P - September 2005

Chapter

8

Troubleshoot Your Controller

Table 8.199

Module Status LED MS

Possible Cause

Correction

OFF

No power at module.

Switch on the power supply.

Green

module is in standby mode.

None

Green flashing

module not configured.

Verify the correct setting of
the MAC ID.

Red flashing

Invalid configuration

Check configuration data.

RED

Module error which can not
be resolved.

Replace the module.

Table 8.200

Network Status LED NS

Possible Cause

Correction

OFF

module without power or

communication is blocked at
this channel because

of bus-off state or

power loss or

the channel was
blocked explicitly.

Switch on the module,

supply the mains voltage to
the channel and

ensure that the channel is
active.

Green

Although the channel is
enabled, communication is
not possible.

Check the communication
function at the master
programmable controller.

Green flashing

Normal mode

None

Red flashing

Communication error or the
module may be defective.

Reset the module. If further
errors occur, replace the
module.

RED

Communication error.

Check the master
programmable controller.