Publication 1760-UM003A-EN-P - September 2005
Pico GFX Control Commands 7-27
Block Transfer: BT01 – BT32
Table 6.111 Telegram Structure
Byte
Meaning
Value (hex), sent by
Maste
r
Slav
e
Master
Slave
Attribute ID
Read
92
–
Write
B2
–
0
Response:
Read successful
–
C2
Write successful
–
C1
Command rejected
–
C0
0
1
Type
26
26
1
2
Instance
01 – 20
01 – 20
2
3
Index
Table 6.112
Table 6.112
3 – 6
4 – 7
Data 1 – 4
Read operation
00
depending on index,
Table 6.113, 6.114
Write operation
depending on index,
Table 6.113, 6.114
00
Table 6.112 Operand overview
Index
(hex)
Operand
read
write
00
Bit IO, Table 6.113
x
01
Mode, Table 6.114
x
02
Source range 1
I1
x
c
(1)
(1) The value can only be written if it is assigned to a constant in the program.
03
Target range 2
I2
x
c
04
Number of elements to compare: max. 192 bytes
NO
x
c
TIP
The data for index 2 and 3 is transferred as a 32-bit
value in Intel format (Data 1 – Low Byte .. Data 2 -
High Byte).