7-50 Pico GFX Control Commands
Example: Index 2 – 5, Parameter channels A – D
The channel A parameters of year time switch HY14 are to be written.
Table 6.161 Index 2 – 5, Parameter channels A – D
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 2
Date 1
ON
y6
(1)
(1) y6 ... y0: Year (0: 2000 .. 99: 2099)
y5 y4 y3 y2 y1 y0 m3
(2)
(2) m3 ... m0: Month (1 .. 12)
m2
m1
m0
d4
(3)
(3) d4 ... d0: Day (1 .. 31)
d3
d2
d1
d0
Year
Month
Day
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 4
Date 3
OFF y6
y5 y4 y3 y2 y1 y0 m3
m2
m1
m0
d4
d3
d2
d1
d0
Year
Month
Day
Table 6.162 Switch-on Time
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 2
Date 1
ON
0
0
0
0
0
1
1
0
1
1
0
0
1
1
1
0
Year
(1)
(1) Year = 2003 = 03hex = 0000 0011bin
Month
(2)
(2) Month = 6 (June) = 06hex = 0000 0110bin
Day
(3)
(3) Day = 14 = 0Ehex = 0000 1110bin
Table 6.163 Switch-off Time
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 4
Date 3
OFF
y6
y5
y4
y3
y2
y1
y0
m3
m2
m1
m0
d4
d3
d2
d1
d0
Year
(1)
(1) Year = 2012 = 0Chex = 0000 1100bin
Month
(2)
(2) Month = 10 (October) = 0Ahex = 0000 1010bin
Day
(3)
(3) Day = 3 = 03hex = 0000 0011bin