Table 6.55 – Rockwell Automation 1760-DNET Pico DeviceNet Communications Module User Manual User Manual

Page 73

Advertising
background image

Publication 1760-UM003A-EN-P - September 2005

Application Examples for Pico 6-29

Meaning:

The values appear in the Parameter menu. The time is used in the
impulse transmitter mode with the Second time base. The time
setpoint S1 is assigned a constant and the time setpoint S2 is assigned
a variable such as I7, I8 C2...etc.

Explanation:

Data 1 = 4C

Data 2 = 06

l resulting 16-bit value = 064C

hex

= 1612

dec

Table 6.55 Index 01 – Control byte

FB input/output Data 3

Bit

7

6

5

4

3

2

1

0

ST

(1)

(1) Stop, the timing relay is stopped (Stop coil)

RE

(2)

(2) Reset, the timing relay is reset (reset coil)

EN

(3)

(3) Enable, the timing relay is started (trigger coil)

Q1

(4)

(4) Switch contact

Table 6.56 Read Time Setpoint 1

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Command: Read

89

Response: read successful

C2

1

Type

8E

8E

2

Instance

00

00

3

Index

03

03

4

Data1

00

4C

5

Data 2

00

06

6

Data 3

00

00

7

Data 4

00

00

Table 6.57 Set Time

millisecond

s

16120 ms

16.120 s

Seconds

M:S

1620 s

26:52 Minutes

Minute

H:M

1612 min

67:04 Hours