Command table (4 of 13) – Hypertherm HPR260 Manual Gas Preventive Maintenance Program Rev.5 User Manual

Page 254

Advertising
background image

APPENDIX B – CNC INTERFACE PROTOCOL

HPR260 Auto Gas

Instruction Manual

b-9

Command table (4 of 13)

ID

Command

System

Description

074

GET_IO_STATUS

Manual gas system
Auto gas system

Read the status of the I/O ports of the DSP. Refer to I/O
listing for description of each bit in Ports A-F.

Data:
None

Return value:
PA00000000 PB00000000 PC00000000 PD00000000
PE00000000 PF00000000
Ports A-F are returned space-delimited. The numbers are the
decimal representation of the binary value of the port. 1 = on,
0 = off.

Sample:
>0749B<
>074PA00000100 PB00000000 PC00010101
PD00100000 PE00010000 PF10000000B7<

078

SET_ALL_GAS_FLOWS

Auto gas system

Set all gas flow rates.

N2 mix setpoint and Gas 2 mix setpoint are only applicable
when using a mixed plasma gas such as H35 – N2.
Otherwise, these 2 values should be set to 0.

A value of 0 for N2 mix setpoint will cause the system to
close SV12, the solenoid valve for N2 mixing. A value of 0 for
Gas 2 Mix Setpoint will cause the system to close SV13 and
open SV14. This will cause the inlet gas to bypass motor
valve 2 and pass directly to the outlet of the mixing console.

Data:
Space-delimited:
Plasma cutflow (0 –99 psi),
Plasma preflow (0 – 99 psi),
Shield cutflow (0 – 99 psi),
Shield preflow (0 – 99 psi),
N2 mix setpoint (0 – 100 psi),
Gas2 mix setpoint (0 – 100 psi).

Return value:
1 = accepted, 0 = not accepted

Sample:
>07855 45 35 25 50 50AB<
>0781D0<

5

Advertising