6 217IF Module

6.5.4 Setting CP-217 Transmission Definitions Data

6-18

The numbers displayed in the tabs at the top of the window (CIR#nn) are the CP-217
circuit numbers. Each 217IF Module requires 3 circuits and the same circuit number
must not be used more than once.

3. Transmission Protocol

Select the desired protocol.

• MEMOBUS: Yaskawa’s standard MEMOBUS protocol.
• MELSEC: Mitsubishi’s special protocol (control protocol type 1) for use with gen-

eral-purpose sequencers and computer links.

• OMRON: OMRON’s SYSMAC C-series Host Link protocol.
• No protocol: Data can be transferred at any time by the user application program.

4. Master/Slave

When the Transmission Protocol has been set to MEMOBUS, MELSEC, or OMRON,
select whether the Machine Controller will operate as a Master or a Slave.

5. Device Address

Select the device address. When the Machine Controller is being used as a Master, set
the device address to 0. When the Machine Controller is being used as a Slave, set the
device address to a unique value between 1 and 63.

6. Serial I/F (Serial Interface)

Select the serial interface.

7. Transmission Mode

Select the transmission mode.

• RTU: Specifies RTU mode when the Transmission Protocol is set to MEMOBUS.
• ASCII: Specifies ASCII mode when the Transmission Protocol is set to MEMOBUS.
• None: Use for MELSEC, OMRON, and no-protocol communications.

8. Data Length

Select the number of bits in one character.

• 8Bit: 8 bits
• 7Bit: 7 bits

9. Parity Bit

Specify whether or not the parity bit will be used.

• Even: Even parity
• Odd: Odd parity
• None: No parity check

10. Stop Bits

Select whether there will be one or two stop bits after each byte.

• 1stop: 1 stop bit

Machine Controller

Circuit Numbers

MP920

1 to 24