Cn3 cables – Yaskawa MP920 Communications Module User Manual

Page 222

Advertising
background image

8.5 Connection to an Inverter

8-31

8

CN3 Cables

Note: 1. Connect the cable so that the terminating resistance for the 217IF is

connected.

2. Set the switch on the board to ON. For the RS-485 intermediate

stations, set the switch on the board to OFF. (VS-616G5)

1. Refer to 8.1.2 Cable Specifications for the MPE720 Programming Device connections.

2. If the terminating resistance cannot be inserted in the Module, mount 120

Ω. terminating resistance

at the end of the transmission line outside the Module. Insert the terminating resistance in the sta-
tions at both ends of the transmission path. Do not insert it in the intermediate stations.

217IF

VS-616G5

MR 8-pin

Screw Terminal

Signal Name

Pin No.

Pin No.

Signal Name

RXR

4

1

SRD (+)

RX (-)

1

2

SRD (-)

RX (+)

2

3

SRD (+)

TXR

5

4

SRD (-)

TX (-)

6

TX (+)

7

SG

8

SH

3

FG

Shield

INFO

Intermediate stations

Stations (at both ends) in which the terminating
resistance is mounted

Advertising