3.2 Protocol Functions

3-7

3

„

MEMOBUS Protocol Functions

3.2.3

MELSEC-A Protocol

The MELSEC-A protocol is used for communications between MELSEC-A Series general-
purpose sequencers manufactured by Mitsubishi Electric Corporation. There is no need to be
aware of the communications protocol. In this case, a special-purpose Ethernet Module
(AJ71E71) and a Computer Link Unit (AJ71UC24) are required for the Mitsubishi
MELSEC-A Sequencers.

„

Communications Using the MELSEC Protocol

The MELSEC protocol is used for communications between a Controller and a MELSEC-A
sequencer.

That is to say, the Master (Controller) transmits the MELSEC format instructions to the Slave
(MELSEC), and receives a response message from the Slave.

When communicating with a MELSEC-A computer, the protocol is automatically converted
inside the 217IF and the 218IF Modules. Therefore, the MSG-SND and MSG-RCV system
functions can be used in the same way as when the Extended MEMOBUS protocol is used by
a user program.

The following three MELSEC functions are supported by Ethernet communications using the
218IF and the AJ71E71:

• Communications between CPUs
• Fixed buffer communications
• Random access buffer communications

With fixed buffer communications, the Controller can be either a Master or a Slave. With
communications between CPUs and random access buffer communications, however, the
Controller will be a Master due to the MELSEC specifications.

With serial communications using the 217IF and the AJ71UC24, the special protocol type 1
is supported. With serial communications, the Controller will be the Master.

Function

Code

Function

No. of Points

Remarks

01H

Coil status read

2,000 points

−

02H

Input relay status read

2,000 points

−

03H

Holding register write

125 words

−

04H

Input register read

125 words

−

05H

Single coil status change

1 point

−

06H

Single holding register write

1 word

−

08H

Loopback

−

−

0FH

Multiple coil status change

800 points

−

10H

Variable register write

100 word

−