3 programming, 4 melsec commands, 218ifa programming suggestions – Yaskawa MP920 Communications Module User Manual

Page 186: Melsec programs

Advertising
background image

7 218IF Module

7.8.3 Programming

7-40

7.8.3

Programming

„

218IFA Programming Suggestions

The 218IFA communicates with the MELSEC Controller that performs Extended MEMO-
BUS and MELSEC message conversion processing. Thus there is no need for the MELSEC
message configuration to be recognized by the user application. The user can easily commu-
nicate with the MELSEC Controller by using the MSG-SND function to specify MELSEC
under Protocol Type in the 218IFA Connection Parameter Window.

Refer to the list of MELSEC commands for the commands that are used by the MSG-SND
function, and the MEMOBUS commands corresponding to the MELSEC commands.

For example, MEMOBUS command 01 or 02 will correspond to MELSEC command 00
(reads bit devices in 1-bit units).

„

MELSEC Programs

The Ethernet Module (AJ71E71) must be initialized by the MELSEC ladder logic program.

Refer to the procedure for refreshing other nodes in the MELSEC manual, and create a lad-
der logic program for initial processing.

7.8.4

MELSEC Commands

The following table shows the common MELSEC ACPU commands that are supported by
the MP900-Series 218IFA Module, and the corresponding MEMOBUS command numbers.

Table 7.8 Common MELSEC ACPU Commands

Command

Description

Qty

218IFA

Support

*

MEMOBUS

Command

00H

Reads bit devices in 1-point units

256 points

Yes

01H/02H

01H

Reads bit devices in 16-point units

128 words

(2,048 points)

No

Reads word devices in 1-point units

256 points

Yes

03H/04H/

09H/0AH

02H

Writes bit devices in 1-point units

256 points

Yes

05H/0FH

03H

Writes bit devices in 16-point units

40 words

(640 points)

No

Writes word devices in 1-point units

256 points

Yes

06H/0BH/10H

04H

Randomly specifies, sets, and resets bit devices and device
numbers in 1-point units

80 points

No

05H

Randomly specifies, sets, and resets bit devices and device
numbers in 16-point units

40 words

(640 points)

No

Randomly specifies, sets, and resets word devices and device
numbers in 1-point units

40 points

Yes

0EH

06H

Sets the bit devices to be monitored in 1-point units

40 points

No