Cp-215 repeater-ts5 cable connections – Yaskawa MP920 Communications Module User Manual

Page 303

Advertising
background image

D.1 In-panel Wiring

D-11

D

„

CP-215 Repeater-TS5 Cable Connections

The following figure shows a CP-215 Repeater-TS5 transmission line connection example.

Fig. D.8 CP-215 Repeater-TS5 Transmission Line Connection Example

• Connect the in-panel twisted-pair cable (YS-IPEV-SB, 1P

× 0.3 mm

2

, manufactured by

Fujikura Corporation) equipped with an MR-8LM(G) connector to the CN1 transmission
connector on the Repeater.

• Connect pins 8 and 1 of the CN1 transmission connector on the Repeater to SRD+ and

SRD-, respectively.

• Connect the CN3 and CN4 optical transmission connectors on the Repeater to a crystal

glass fiber cord or cable (GI-50/125, 1,300 nm, 0.7 to 1 dB) equipped with a single-core
optical connector (FC type).

• If the Repeater is located at the end of the transmission line, short-circuit pins 4 and 5 of

the CN1 to connect the internal 75

Ω terminating resistance.

1

4

5

8

75

Ω

SRD+

SRD-

215IF in-panel cable

CP-215 Repeater-TS5

Terminator

CN1
MR-8LM (G)

CN3: BRX

FC connector

CN4: BTX

GI-50/125, 1300 nm

Advertising