4 cables, 1 215if connection cables – Yaskawa MP920 Communications Module User Manual

Page 73

Advertising
background image

5 215IF Module

5.4.1 215IF Connection Cables

5-12

5.4

Cables

This section explains the cable specifications for 215IF Module communications.

5.4.1

215IF Connection Cables

„

215IF Connector Pin Layout (CN1/215)

MR-8RFA4 (G) connector (manufactured by Honda Communication Industries Co., Ltd.) is
used on the Module. Use an MR-8M (G) (case: MR-8L) connector on the cable.

„

Calculation Example of Maximum Transmission Distance

The following table shows a calculation example for the maximum transmission distance
when 32 stations are connected.

Note: 1. L

0

is when the total length of the cables inside the control panel is

about 55 m and 20 JC215-01 Junction Boxes are used.

2. L

01

and L

02

are when 16 stations are connected on both sides of the

Repeater.

No.

Signal Name

Function

No.

Signal Name

Function

1

SRD-

Sending and receiving
data (-)

5

N.C.

Not connected

2

N.C.

Not connected

6

N.C.

Not connected

3

N.C.

Not connected

7

N.C.

Not connected

4

N.C.

Not connected

8

SRD+

Sending and receiving
data (+)

Transmission

Speed

Cable Length

between Control

Panels

L

0

: No Repeaters

Total Wiring Distance

L

01

: One Repeater

L

02

: Two Repeaters

4 Mbps

170 m or less

600 m

1,100 m

2 Mbps

270 m or less

900 m

1,550 m

1 Mbps

420 m or less

1,400 m

2,350 m

Advertising