7 218IF Module

7.2.1 218IF Module

7-6

The following table describes the operation of the LED indicators when a failure has
occurred.

Note: The number in parentheses ( ) under “Flashing” indicates the number

of flashes.

The table below shows differences between 218IF Module and 218IFA Module.

Table 7.1 Indicator Displays for Errors

Failure

Error Description

Indicators

RUN

ERR

TX

RX

PROM Checksum
Error

A PROM checksum
error was detected dur-
ing online self-diagnosis.

Not lit

Flashing
(1)

Depends on the cir-
cumstances.

SRAM Error in Mod-
ule

A hardware error was
detected during online
self-diagnosis.

Not lit

Flashing
(2)

Not lit

Not lit

CPU Interface Error

A data transmission error
was detected between
Module and CPU during
online self-diagnosis.

Not lit

Flashing
(3)

Not lit

Not lit

Transmission Error

Transmission data error

Lit

Lit

Depends on the cir-
cumstances.

Watchdog Timer

Watchdog timer error

Not lit

Flashing
(15)

Depends on the cir-
cumstances.

Description

218IF

218IFA

Model Number

JEPMC-CM210

JEPMC-CM210A

External
Appearance

Specifications

• 10Base-5
• Requires a conversion transceiver to

be externally connected for conver-
sion to 10Base-T

• 10Base-T

Connector 1

• AUI Connector (15 pin D-sub)

• Modular jack

Connector 2

• BL3.5/2F-AU (Weidmuller)

For +12-VDC power supply

• None