D.1 In-panel Wiring

D-13

D

D.1.3 In-panel Wiring Separation

• Nonshielded in-panel cables must be thoroughly separated from low-voltage cables.

If this is difficult, shield the low-voltage cables.

• Shielded in-panel cables must be thoroughly separated from high-voltage cables.

If this is difficult, shield the high-voltage cables.

D.1.4 Shield Treatment

• Connect the shield of each shielded in-panel twisted-pair cable to the Es ground terminal

so that it does not loop.

D.1.5 Exposed Conductor Length

• The exposed conductor length of each in-panel twisted-pair cable should be as short as

possible (50 mm or less).

• The characteristic impedance of the exposed conductor section is greater than the pre-

scribed value (75

Ω).

• Increasing the exposed conductor length increases transmission waveform distortion,

resulting in a transmission error.

50 mm max.

Twisted-pair cable