Holding register read (extended) – Yaskawa MP920 Communications Module User Manual

Page 258

Advertising
background image

B.1 Extended MEMOBUS Messages

B-9

B

„

Holding Register Read (Extended)

MFC: 20H

SFC: 09H

Length: 08H

SPARE

CPU No.

Set the command length.

Command

The SFC number is 09H when the holding register contents are

read.
Set 4 bits each for the destination CPU number and the source

CPU number.

Set the leading address of the holding registers to be read.

Set the number of holding registers to be read.

(L)

(H)

Reference No.

No. of registers (n)

(L)

(L)

(H)

(H)

7

0

Always 20H.

MFC: 20H

SFC: 09H

Length: 06H+

SPARE

CPU No.

Data 1

Data n

(L)

(H)

(L)

(H)

(L)

(H)

(L)

(H)

Set the command length.

Response

Always 20H.
The same SFC number as that specified in the command is

returned.
Set 4 bits each for the destination CPU number and the source

CPU number.

The holding register contents are returned.

The number of read holding registers is returned.

7

0

No.of registers×2

No. of registers (n)