Yaskawa MP920 Communications Module User Manual

Page 165

Advertising
background image

7.5 CP-218 Transmission Definitions

7-19

7

11. Code

Handle the code for the data to be transferred at each connection according to the code
set at the remote station.

• RTU:

Specifies RTU mode when the MEMOBUS protocol is being used.

• ASCII: Specifies ASCII mode.
• BIN:

Specifies binary mode.

The codes that can be selected depend on the data in the Protocol Type column.

Note: Yes: Selectable, No: Not selectable

12. DST. Station (Remote Station’s Name)

Enter a connection comment of up to 32characters.

Protocol Type

Remarks

Extended
MEMOBUS

Yaskawa Extended MEMOBUS protocol.

MEMOBUS

Yaskawa Standard MEMOBUS protocol.

MELSEC

Mitsubishi Electric’s Ethernet Interface protocol for use with general-
purpose sequencers.

No protocol

General-purpose message communications. Data is transmitted and
received without being processed into consecutive MW registers.

Table 7.4 Selectable Codes

Protocol Type

Code

RTU

ASCII

BIN

Extended MEMOBUS

No

Yes

Yes

Extended MEMOBUS

No

Yes

Yes

MEMOBUS

Yes

Yes

No

MELSEC

No

Yes

Yes

No protocol

No

Yes

Yes

Advertising