Direct connection method, Calculating the maximum transmission distance – Yaskawa MP920 Communications Module User Manual

Page 313

Advertising
background image

D.4 Wiring Optical Fiber Cables

D-21

D

Direct Connection Method

This method directly connects optical fiber cables outside a control panel to optical connec-
tors inside the control panel.

„

Calculating the Maximum Transmission Distance

The maximum transmission distance differs according to the method for connecting optical
fiber cables inside a control panel to optical fiber cables outside the control panel or connect-
ing optical fiber cables between control panels (fusing connection or connector relay connec-
tion) as well as the connection position.

Calculating the Maximum Transmission Distance for the 215IF
Repeater-TS2

Where,

PL = Po - Pi - Pm (dB)

= -18 + 28 - 1.5
= 8.5 (dB)

PL: Allowable loss for optical sending and receiving (8.5 dB)

Po: Optical sending level (-18 dBmp)

Pi: Optical receiving level (-28 dBmp)

Control panel

Two-core crystal glass
optical fiber cable

Control panel

Terminal box

Terminal box

Optical Repeater

Optical connector: FC

Optical Repeater

Optical connector

Conversion Adapter: 0D-9384, manufactured by NEC

Control panel

Two-core crystal glass
optical fiber cable

Control panel

Optical Repeater

Optical Repeater

Optical connector

(km)

Pc (dB / km)

PL - Ps - Pa (dB)

=

L

Advertising