Appendix D Wiring Communications

D.2.2 Panel-to-Panel Cables

D-16

D.2.2 Panel-to-Panel Cables

The following table shows the panel-to-panel cables used for communications.

Always use the specified cables. Otherwise, the communications system will fail to provide
its full performance.

When bending a communications cable, be sure that the bending radius is at least 10 times
the finished outer diameter of the cable.

D.2.3 Wiring Separation

• House the shielded communications cables in a low-voltage circuit duct that is different

from general operation circuit ducts. If this is not possible, keep the low-voltage circuits
at least 100 mm away from the general control circuits.

• Likewise, keep the shielded communications cables at least 300 to 1,200 mm from the

main circuits.

D.2.4 Shield Treatment

• Ground the shield at one point only for panel-to-panel cables.

• Using a ground wire of 8 mm

2

or greater, ground the shielded ground trunk cable to an

independent ground pole with a ground resistance of 100

Ω or less.

D.2.5 Exposed Conductor Length

• The exposed conductor length of each panel-to-panel twisted-pair cable should be as

short as possible (100 mm or less).

• The characteristic impedance of the exposed conductor section is greater than the pre-

scribed value (75

Ω).

• Increasing the exposed conductor length increases transmission waveform distortion,

resulting in a transmission error.

Table D.3 Cable Bending Radius

Communications

System

Cable Type

Finished

Outer

Diameter

dl (mm)

Permissible

Bending

Radius

10 dl (mm)

Applicable Duct

215IF,
217IF RS-485

Twisted-pair cable:
YS-IPEV-S (Cu), 1P

×

1.25 mm,

manufactured by Fujikura Corpo-
ration

8.6

86 min.

Low-voltage
duct

CP-215
Repeater

Coaxial cable:
5C-2V (Cu, Fe)-ZV, manufac-
tured by Fujikura Corporation

12.0

120 min.

Low-voltage
duct

100 mm max.

Twisted-pair cable