OMRON Commands Supported by the 217IF
The following table shows the OMRON SYSMAC commands that are supported as MEMO-
BUS commands by the 217IF Module.
Transmission Parameter Settings
The following diagram shows the Transmission Parameter Settings Window in which the
OMRON protocol is specified.
When using the OMRON protocol, specify “OMRON” as the communications protocol in
the CP-217 Transmission Settings Window.
Table 3.5 List of OMRON Commands
MEMOBUS
Command
OMRON
Header Code
Description
No. of Words
Remarks
01H
RR
Reads IR/CIO and AR Area words
256 words
−
03H
RD
Reads DM area words
2,000 words
−
0FH
WR
Writes IR/CIO and AR Area words
252 words
−
10H
WD
Writes DM area words
2,000 words
−
08H
TS
Test
−
−
Master
Function
IC
Undefined command error (response
only)
−
−