Omron commands supported by the 217if, Transmission parameter settings – Yaskawa MP920 Communications Module User Manual

Page 43

Advertising
background image

3.2 Protocol Functions

3-11

3

„

OMRON Commands Supported by the 217IF

The following table shows the OMRON SYSMAC commands that are supported as MEMO-
BUS commands by the 217IF Module.

„

Transmission Parameter Settings

The following diagram shows the Transmission Parameter Settings Window in which the
OMRON protocol is specified.

When using the OMRON protocol, specify “OMRON” as the communications protocol in
the CP-217 Transmission Settings Window.

Table 3.5 List of OMRON Commands

MEMOBUS

Command

OMRON

Header Code

Description

No. of Words

Remarks

01H

RR

Reads IR/CIO and AR Area words

256 words

−

03H

RD

Reads DM area words

2,000 words

−

0FH

WR

Writes IR/CIO and AR Area words

252 words

−

10H

WD

Writes DM area words

2,000 words

−

08H

TS

Test

−

−

Master
Function

IC

Undefined command error (response
only)

−

−

Advertising