Appendix A System Functions

A.1.3 Parameter Details

A-8

1. Read/write request for coils or relays: Set the leading bit address of the data.

2. Continuous read/write request for registers: Set the leading word address of the data.

3. Discontinuous read/write request for registers: Set the leading word address of the

address table.

The following data address setting range is used for no-protocol transmissions.

„

Data Size (PARAM06)

Set the size (number of bits or words) of the data to be read or written.

The setting range differs according to the function code.

33H

MELSEC random buffer write

0 to 32767 (0 to 7FFFH)

2

(cont’d)

Function

Code

Function

Data Address Setting Range

215IF, 218IF,

MECHATROLINK

217IF, Serial

F#

Function

Data Address Setting Range

-

-

0 to 32767 (0 to 7FFFH)

Function

Code

Function

Data Address Setting Range

215IF, 218IF

217IF, Serial

MECHATROLINK

00H

Not used.

Not valid.

01H

Coil status read

Bits 1 to 2000 (1 to 07D0H)

02H

Input relay status read

Bits 1 to 2000 (1 to 07D0H)

03H

Holding register read

Words 1 to 125 (1 to 007DH)

04H

Input register read

Words 1 to 125 (1 to 007DH)

05H

Single coil status change

Not valid.

06H

Single holding register write

Not valid.

07H

Not used.

Not valid.

08H

Loopback test

Not valid.

09H

Holding register read (extended)

Words 1 to 508 (1 to
1FCH)

Not valid.

Words 1 to 252 (1 to
00FCH)

0AH

Input register read (extended)

Words 1 to 508 (1 to
1FCH)

Not valid.

Words 1 to 252 (1 to
00FCH)

0BH

Holding register write (extended)

Words 1 to 507 (1 to
1FBH)

Not valid.

Words 1 to 252 (1 to
00FBH)

0CH

Not used.

Not valid.

0DH

Discontinuous holding register read
(extended)

Words 1 to 508 (1 to
1FCH)

Not valid.

Words 1 to 252 (1 to
00FCH)

0EH

Discontinuous holding register write
(extended)

Words 1 to 254 (1 to
0FEH)

Not valid.

Words 1 to 126 (1 to
007EH)

0FH

Multiple coil status change

Bits 1 to 800 (1 to 0320H)

10H

Multiple holding register write

Words 1 to 100 (1 to 0064H)