A.1 SEND MESSAGE Function (MSG-SND)

A-9

A

The following setting range is used for no-protocol transmissions.

„

Remote CPU Number (PARAM07)

Set the remote CPU number.

When the transmission destination is the CP-317, CP-9200SH, or CP-9200, set 1 or 2. When
the destination is the CP-3500H, set 1, 2, 3, or 4. In other cases, set 0.

„

Coil Offset (PARAM08)

Set the offset word address of the coils.

This parameter is valid when the function code is 01H, 05H, or 0FH.

„

Input Relay Offset (PARAM09)

Set the offset word address of the input relays.

This parameter is valid when the function code is 02H.

„

Input Register Offset (PARAM10)

Set the offset word address of the input registers.

This parameter is valid when the function code is 04H or 0AH.

„

Holding Register Offset (PARAM11)

Set the offset word address of the holding registers.

This parameter is valid when the function code is 03H, 06H, 09H, 0BH, 0DH, 0EH, or 10H.

31H

MELSEC fixed buffer communications

Words 1 to 507 (1 to
1FBH)

Not valid.

Not valid.

32H

MELSEC random buffer read

Words 1 to 508 (1 to
1FCH)

Not valid.

Not valid.

33H

MELSEC random buffer write

Words 1 to 508 (1 to
1FCH)

Not valid.

Not valid.

(cont’d)

Function

Code

Function

Data Address Setting Range

215IF, 218IF

217IF, Serial

MECHATROLINK

Data Address Setting Range

217IF

218IF

215IF

No-protocol 1

Words 1 to 254

Words 1 to 510

Words 1 to 510

No-protocol 2

Bytes 1 to 508

Bytes 1 to 1020

Bytes 1 to 1020