D.2 Indoor Panel-to-Panel Wiring

D-15

D

„

217IF RS-485 Panel-to-Panel Cable Connections

The following figure shows a 217IF RS-485 panel-to-panel cable connection example.

Fig. D.10 217IF RS-485 Panel-to-Panel Cable Connection Example

• Connecting Signal Lines

Use panel-to-panel cables to connect the incoming and outgoing SRD+ and SRD- signal
terminals on each control panel as shown in the above figure.

• Connecting Terminating Resistances

Mount terminating resistances at both ends of the transmission line.

• Connecting Shielded Ground Trunk Cables

Connect the shield of each panel-to-panel cable to shielded wire junction terminal S on
each control panel and ground it at one point only.

Using a ground wire of 8 mm

2

or greater, ground the shield to an independent ground

pole with a ground resistance of 100

Ω or less.

120

Ω

+

-

SRD S

+

-

+

-

SRD

SRD

S

+

-

SRD

S

E

120

Ω

8 mm

2

Independent ground
pole: 100

Ω or less

S

Panel-to-panel
cable