2 melsec communications, Melsec communications specifications – Yaskawa MP920 Communications Module User Manual

Page 138

Advertising
background image

6 217IF Module

6.6.2 MELSEC Communications

6-22

6.6.2

MELSEC Communications

„

MELSEC Communications Specifications

The following table shows the general specifications for MELSEC communications, and
which of these specifications are supported by the MP900.

000003

Other MEMOBUS Device

Coil

MP 900

Coil

MP 900

Coil

000002
000001

MB000002
MB000001
MB000000

MB001002
MB001001
MB001000

(Offset: Default is 0)

(Offset: 100)

MEMOBUS message

Table 6.8 MELSEC Communications Specifications

Item

General MELSEC Specifications

MELSEC Specifications Supported by

the MP900

Transmission Method

RS-232C: Half-duplex, full-duplex
RS-422: Half-duplex

RS-232C: Full-duplex
(Half-duplex for procedural)
RS-485: Half-duplex

Synchronization

Start-stop synchronization

Start-stop synchronization

Transmission Speed

300/600/1200/2400/4800/9600/19200 bps

1200/2400/4800/9600/19200 bps

Data Format

Data: 8 or 7 bits
Parity: Odd, even, none
Stop bits: 1 or 2 bits

Data: 8 or 7 bits
Parity: Odd, even, none
Stop bits: 1 or 2 bits

Error Detection

With or without checksum

With checksum

DTR/DSR (ER/DR)
Control

Yes/No (RS-232C only)

Both controls are
possible.

None

DC1/DC3, DC2/DC4
Control

Yes/No

Transmission Protocol

Special protocol

Only protocol type 1 is supported.

Type 1

(1:1, 1:N, N:N)

Type 2

Type 3

Type 4

No protocol (1:1, 1:N)

Full duplex (1:1)

Advertising