Omron devices – Yaskawa MP920 Communications Module User Manual

Page 146

Advertising
background image

6 217IF Module

6.6.3 OMRON Communications

6-30

„

OMRON Devices

The table below shows the OMRON devices (bits and data memory) that can be accessed
from the MP900.

The MP900 register numbers corresponding to the OMRON device range and the MEMO-
BUS commands used are also shown in the table.

* 1. MEMOBUS Command

01H/0FH: Coils
03H/10H: Holding registers

* 2. Register number offsets can be specified for both input registers and holding registers by the

MSG-SND and MSG-RCV system functions.

Table 6.14 List of OMRON Addresses

Name

Words

Bits

MEMOBUS

Command*

1

Leading No.

Register No.*

2

I/O Relay

000 to 039

00000 to 03915 01H/0FH

0 to 639

MB000000 to MB00039F

Internal Auxiliary Relay

040 to 246

04000 to 24615 01H/0FH

640 to 3951

MB000400 to MB00246F

Special Auxiliary Relay

247 to 255

24700 to 25507 01H/0FH

3952 to 4088

MB002470 to MB002557

Data Memory

0000 to 9999

DM 0000 to
DM 9999

03H/10H

0000 to 9999

MW00000 to MW09999

Advertising