3.2.5 No Protocol Mode (Through Mode)

3-12

3.2.5

No Protocol Mode (Through Mode)

„

Overview

With the no protocol mode, consecutive data in the Controller’s holding registers (MW regis-
ters) is transferred as it is.

„

No Protocol Functions

„

Transmission Parameter Setting Example

The following Connection Parameter Settings Window is displayed when the Through Mode
is used.

When using the Through Mode, specify “None” in the protocol type column in the Connec-
tion Parameter Window.

Fig. 3.5 Connection Parameter Window

„

Communications Programs

Through Mode communications can be performed by specifying No-protocol 1 (value = 2) or
No-protocol 2 (value = 3) as protocol type PRO-TYP in the MSG-SND and MSG-RCV func-
tions in the user program. With No-protocol 1 communications, data is transferred in word
units. With No-protocol 2 communications, data is transferred in byte units.

Refer to Appendix A System Functions for information on using the MSG-SND and MSG-
RCV functions.

Function Code

Function

Qty

Remarks

Receives messages in word units.

Message function
PRO_TYP = 2

Receives messages in byte units.

Message function
PRO_TYP = 3